Water Leak Alarm/Detector
61F-WLA/-GPN-V50
CSM_61F-WLA_61F-GPN-V50_DS_E_5_4
Flexible Setup according to Water Quality
and Surrounding Wiring Conditions
• The operating resistance has a variable sensitivity from 0 to
50 k , so the best set values can be made according to the
predicted water leakage, degree of overflow, water quality, or
surrounding wiring conditions.
• The power supplied to the Sensing Band is 24 VAC, so operation is stable because there is no electrode deterioration from
electrical corrosion.
• A contact signal output enables monitoring from remote locations.
[Reference]
For detecting leakage of water with high resistivity, use K7L-U/-UD ultra
high-sensitivity models.
Note: Manufacturing of the 61F-WLA was discontinued at the
end of September 2016.
Refer to 7EJIX]4VIGEYXMSRWJSV*PSEXPIWW0IZIP
'SRXVSPPIVW.
Ordering Information
Water Leak Alarm
Water Leak Detector
When ordering, to complete the part number, be sure to specify the
desired operating voltage.
61F-WLA *
61F-GPN-V50
)\EQTPI*;0%?:%'A
* Manufacturing was discontinued at the end of September 2016.
(IWMVIHWYTTP]ZSPXEKI
Specifications
Ratings/Characteristics
Item
Water Leak Alarm
Water Leak Detector
61F-GPN-V50
Model
61F-WLA
Supply voltage
Operating voltage range
Interelectrode voltage
Operating current
110/220, 120/240 VAC
85% to 110% of rated voltage
24 VAC
3 mA (AC) max.
24, 110, 120, 220, 230, 240 VAC
Power consumption
8.0 VA max.
Variable (0 to 50 k )
3.2 VA max.
Sensitivity
Sensitivity error
Indicator
Scale 0: 0 to 10 k *1
Scale 50: 50 10 k
3 A 250 VAC, SPDT cos =1
1 A 250 VAC, SPDT cos =0.4
Provided (Power and Leak indicators)
Alarm buzzer
Test switch
Ambient temperature
Ambient humidity
Accessories
Approved standards
Provided
Provided
–10 to 50C
45% to 85%
Hold-down clip PFC-N8 *2
–
Contact ratings
3 A 250 VAC, DPDT cos =1
1 A 250 VAC, DPDT cos =0.4
Provided (Operation indicator)
Not provided
Not provided
UL508
CSA C22.2 No.14
EN61010-1
EN61326-1
Industrial electromagnetic environment
*1 The Detector may not operate around the setting value of “0.” Adjust the sensitivity depending on the actual application.
*2 Hold-down clip PFC-N8 is attached only 61F-GPN-V50.
*;0%+42:
3TIVEXMSR
-RXIVREP'MVGYMX
'SRRIGXMSRW
*;0% ;EXIV0IEO %PEVQ
*YWI
4S[IV
WYTTP]
0)(
:
:
%PEVQ0)(
0IZIP
HIXIGXMSR
W[MXGLMRK
GMVGYMX
6IGXMJMGEXMSR
WQSSXLMRK
GMVGYMX
%QTPMJMGEXMSR
GMVGYMX
<
&>
%PEVQFY^^IV
:
:
6IGXMJMGEXMSR
WQSSXLMRK
GMVGYMX
:
8IWXW[MXGL
61F-WLA AC120/240 E 价格&库存
很抱歉,暂时无法提供与“61F-WLA AC120/240 E”相匹配的价格&库存,您可以联系我们找货
免费人工找货